The six stage electronic programmable controllers provide
proportional control of outside and return (mixed air) dampers
in sequence with staged heating and cooling equipment.
Programming of the heating and cooling stages and relay
assignment of heating and/or cooling plus operating level are
accomplished by dual-in-line package (DIP) switches.
Proportional heating and cooling outputs are available for
valves or electric heat coils. The six stages can be
programmed for heating, cooling, humidification, night
setback and fan operation.
The heating, cooling and ventilation are precisely controlled
from a single sensor operating with the programmable
controller which employs a single temperature setpoint. (The
CP-8261-333 setpoint is concealed while the CP-8261-702
setpoint is exposed). A nullband adjustment is also provided
for separating the heating and ventilating/cooling functions
between 2 and 14°F. Fan operations may be programmed to
cycle in the unoccupied mode.
Features- Sequenced Control: Staged and/or proportional heating,
proportional control of outside and return (mixed air) damper,
staged and/or proportional cooling. Heating and cooling
cannot operate simultaneously.
-
Single Setpoint (SPB): 55 to 85°F (13 to 29°C). Heating,
cooling and ventilation are controlled from a single sensor
and a single setpoint.
-
Nullband Adjustment (SPA): 2 to 14°F (0 to 8°C); factory
set at 3°F (2°C). Provides for separating the heating and
ventilation/cooling.
-
Mixed Air Low Limit Setpoint (SPC): 41 to 95°F (5 to
35°C).
-
Relay Rating: 24/120 Vac, 1 amp. 240 Vac, 0.5 amp
inductive. See Table 1.
-
Adjustments: (For other adjustments See Table 2).
Minimum Position, Minimum mixed air damper position
(0 to 100%) factory set at 25%.
-
Mixed Air Start Point: Factory set OP3 is 9 Vdc when
IO2 is at 6 Vdc. The M.A.S.P. can be adjusted so that OP3
is 9 Vdc when IO2 is 3 Vdc.
-
Unit Fan: May be programmed to cycle in the unoccupied
mode.
-
Relay Output: 6 relays can be programmed for heating,
cooling or fan operation. Operational voltage level by
dual-in-line switches.
-
Mixed Air Sensor (optional): The controller can provide a
separate mixed air control, or limit control in conjunction with
proportional cooling output ramp.
-
Cold Start: On power failure.
-
Sensors: Any non-adjustable TS-8000.
-
Control Output Voltage: See Table 2.
-
Power Requirements: 24 Vac, 10 VA.
-
Power Supplies Availabl: 6.2 Vdc, 4 mA; 20 Vdc, 35 mA.
-
These regulated and filtered power supplies must not be
connected to +20, +6.2 or red lead of other supplies.
-
Operating 0 to 140°F (-18 to 60°C).
Humidity: 5 to 95% RH, non-condensing.
-
Locations: NEMA Type 1 indoor only.
-
Connections: Coded screw terminals.
-
Cover: Aluminum.
-
Mounting: Unit is provided with plastic track for panel
mounting.
-
Dimensions: 3-7/8" high x 12" wide x 2-3/4" deep (98 mm x
305 mm x 70 mm).