Underground Feeder and Branch Circuit Cable. 600 Volt. Copper Conductors. Sunlight, Moisture, and Fungus Resistant Overall PVC Jacket.
Overview
Southwire® copper UF-B cable is generally used as feeder to outside post lamps, pumps, and other loads or apparatus fed from a distribution point in an existing building as specified in the 2011 National Electrical Code. UF-B cable may be used underground, including direct burial. Multiple conductor UF-B cable may be used for interior branch circuit wiring in residential or agricultural buildings at conductor temperatures not to exceed 90°C (with ampacity limited to that for 60°C conductors) as specified by the National Electrical Code. UF-B can be used in applications permitted for NMC in Section 334.10(B) of the National Electrical Code. Voltage rating for UF-B cable is 600 volts.
Specifications:
- No. of Conductors: 2
- No. of Strands: 1
- Size (AWG): 10
- No. of Grounds: 1
- Nom. Width (MILS): 518 mils
- Nom. Height (MILS): 215 mils
- Insulation Thickness (MILS): 20 mils
- Jacket Thickness (MILS): 32 mils
- Nominal Total Weight (lbs/1000'): 138 lbs/1000'
- UPC: 032886166105