Note: This part has successfully passed the FM Technical Decision Form TD 221 Testing for the A2L and A3 Refrigerants.
Features:
- Detects all CFC, HFC, and HCFC non-flammable refrigerants including R12, R22, R134a, R404a, R410a, R502, R507 and many others
- Ultra-sensitive detection as low as 0.006 oz/yr
- Dual power sources include rechargeable battery and external DC powered wall adapter (included)
- Visual sensor calibration system (with included reference leak bottle)
- Pinpoints small, medium and large leaks quickly and accurately
- Headphone port allows for optional headset for use in high-noise environments
Specifications:
- Sensing Element: Positive Ion Emission Heated Diode
- Sensitivity: 0.006 oz/yr (stationary) | 0.1 oz/yr (moving probe per SAE J2791)
- Sensor Life: 1 year (typical)
- Warm-Up Time: Approx. 2 minutes
- Response Time: 1 second
- Accuracy: Exceeds SAE J1627
- Operating Temperature: 32°F to 104°F (0°C to 40°C)
- Flow Rate: 90 cc/min (typical)
- Auto-Background Adjust: Yes, automatic mode only
- Leak Indicators: Visible LED at probe tip and audible buzzer (with or without optional headphones)
- Probe Length: Flexible 4.5 ft. (1.37 m) with built-in filter
- Dimensions: 10.5” L x 8.3” W x 5.4” H (26.7 cm x 21.1 cm x 13.7 cm)
- Weight: Approx. 5.1 lb. (2.3 kg)
- Agency Listings: UL file SA9717, SAE J1627, CE-Mark
- Power:
- 12 VDC - internal rechargeable sealed lead acid battery (included)
- 100-240 VAC wall adapter/universal battery charger to charge or run continuously (included)
- Battery Life: 3 hours (typical)
- Warranty: 3 years (does not cover sensors, filters, reference leaks, airflow balls, lamps, batteries or probe tips)
Warranty Registration Form