Exact replacement for my discontinued control board. Easy replacement!
Redgren
Waynesville, OH
4 years ago
Verified Buyer
Was this review helpful to you?
Drop in replacement worked fine
Successful drop-in replacement a failing 17B0001N01. All cables connected same as old without any problem.
Comparing all jumpers and dip switches no changes needed for me. But first time installing was a little surprising to me the need to cut line JW3 after researching this is required for geothermal (water-source) heat pump . Momentarily shorting TEST pens causes LED to flash its last status. Cross checking the manual the 4 flashes I received guided to this possibility and and found same configuration on old board.
Attached image is old failing board that had been in service for 16 years. Multiple resistors discolored and not measuring in spec. Run capacitor also needed replacing.
Manual easily searchable but would be nice if SupplyHouse linked. Well packed.