The P29 combines a pressure
sensing mechanism with a time
delay. A drop in pressure
energizes the time delay relay
which opens a contact after a
predetermined time period.
Two Prrincipal Applications:
1. Chiller Low Temperature Cutout
: Pressure element is
connected to the suction side
of a chiller refrigeration
system and the time delay
relay is wired to the
compressor control circuit.
Prolonged low suction
pressure, such as pressure
caused by a low temperature
condition, will cause the
control to shut down the
refrigeration compressor.
On any electrically
driven machine with a forced
oil system, the pressure
element is connected to the
lube oil system and the time
delay relay is wired in the
control circuit. The control
time delay allows oil pressure
to build up to normal on
start-up or recover from
temporary fluctuations. A
sustained loss of oil pressure
will cause the control to shut
down the machine.