Reznor Transformers are replacement electrical components used to restore control power and ignition function in Reznor gas-fired unit heaters and duct furnaces. Contractors turn to this category when a heater loses spark, drops 24 volt control power, or trips on a control fault traced back to a failed primary-to-secondary winding. The lineup includes control transformers such as the 175265 model, rated 30 VA and stepping 115 volts down to 24 volts for the gas valve and thermostat circuit, alongside higher-capacity 40 VA units built for both standard 120 volt and 460 volt three-phase installations. Ignition transformers round out the group, supplying the high-voltage spark that lights the burner on models like the RA110, RA140, RA235, and RA350. Matching the exact VA rating and primary voltage to the heater's rating plate keeps control boards and gas valves protected from under- or over-powering.
Subcategories
Buying Guide
Start with the rating plate on the unit heater itself, since primary voltage (120V or 460V), secondary voltage (typically 24V), and VA rating are stamped there or listed in the wiring diagram inside the control panel. Installing a transformer with too low a VA rating causes the secondary voltage to sag under load, leading to erratic gas valve operation or control board resets. Installing one with too high a VA rating rarely causes damage but adds unnecessary cost.
Next, confirm whether the failure is on the control side or the ignition side. A heater with no 24 volt output at the gas valve terminals, but with 120 volt power confirmed on the primary side, points to a bad control transformer. A heater that has control power but produces no spark at the electrode points to an ignition transformer instead. Testing with a multimeter across the primary and secondary leads before replacing parts avoids paying twice for a diagnosis that a five-minute continuity check would have caught.
Reznor Transformers are model-specific parts, so cross-reference the OEM part number stamped on the failed unit or the model and serial number of the heater rather than relying on physical size alone. Two transformers can look identical but carry different VA ratings or mounting brackets. Keeping the old part on hand during installation confirms lead length and connector style match before the heater goes back into service.
Frequently Asked Questions
What VA rating does a Reznor control transformer need?
VA rating on a Reznor control transformer should match the original part listed on the heater's wiring diagram or rating plate, commonly 30 VA or 40 VA depending on the model. A transformer rated too low for the connected load can cause the 24 volt output to sag and the gas valve or ignition control to behave erratically. Checking the OEM part number is more reliable than guessing based on physical size.
How can a technician tell if a Reznor transformer has failed?
A failed control transformer typically shows no 24 volt reading at the secondary terminals even though 120 volt or 460 volt power is present on the primary side. A failed ignition transformer produces no visible spark at the electrode despite the ignition control calling for spark. A multimeter check across both sides of the transformer confirms which component has failed before parts get ordered.
Can a 120 volt transformer replace a 460 volt unit on a Reznor heater?
Substituting a 120 volt primary transformer into a heater wired for 460 volt three-phase service overloads the winding and burns it out almost immediately. Reznor unit heaters built for 460 volt supply require a transformer rated specifically for that primary voltage, such as the 40 VA model built for 460 volt input. Checking the heater's electrical data plate before ordering avoids this mismatch.
What is the difference between a control transformer and an ignition transformer on a Reznor heater?
A control transformer steps line voltage down to 24 volts to power the thermostat circuit, gas valve, and control board, while an ignition transformer produces the high-voltage spark that lights the burner. Both parts sit inside the same control compartment but serve different functions and fail independently of each other. Diagnosing which circuit lost power narrows down which transformer needs replacement.
Are Reznor ignition transformers interchangeable across unit heater models?
Ignition transformers built for specific Reznor model lines, such as the RA110, RA140, RA235, and RA350 series, are matched to those units' spark gap and mounting requirements. Using a transformer built for a different model line risks a poor mounting fit or incorrect spark output. Matching the SKU to the heater model listed in the parts catalog keeps the ignition system working as designed.