The LC1D40AG7 is a TeSys D 3-pole Contactor with 3NO power pole and 1NO-1NC auxiliary contacts. TeSys D contactor is designed for perfect integration in control systems. It can be used to create motor starters for any type of application.
AC-1 and AC-3 utilization category
Rated operational voltage of 690VAC at 25Hz to 400Hz and 690VDC for power circuit
Rated operational current of 60A at <440VAC (AC-1) & 40A at <440VAC (AC-3) for power circuit
22kW at 415VAC to 440VAC, 50Hz/60Hz Motor power
120VAC at 50Hz/60Hz Control circuit voltage
UL94V-1 Flammability rating
-5 to 60°C Ambient operating temperature range
IP2x front face conforming to IEC 60529 standard protection rating
5.4W (AC-1) and 2.4W (AC-3) Power dissipation per pole
Rated breaking capacity of 800A at 440V for power circuit conforming to IEC 60947 standard