Electronic-Pneumatic Transducers are used in electronic-pneumatic control systems to convert a proportional electric output signal from a controller into a direct-acting, proportional pneumatic signal.
Features - Screw mounting or snap rail (models with cover).
- Factory calibrated.
- Dual barb fittings.
- High accuracy.
Specifications- Application: Electric to pneumatic Transducer
- Maximum Safe Operating Pressure (psi): 30 psi
- Output Pressure Range: 3 to 15 psi
- Connections: Dual barb-fittings for 1/4 in. or 5/32 in. O.D. plastic tubing
- Airflow Usage: 0.025 scfm (117mL/s)
- Max. Operating Temperature: 131 F
- Input Signal: 2 to 10 Vdc
- Normal High End Pressure: 16 psi with 18 psi main pressure at 12 Vdc
- Normal Low End Pressure: 0.5 psi at 0 Vdc
- Pressure Range: 0 to 18 psi
- Voltage: Powered by Control signal
- Humidity Range: 5 to 95% RH