| Application: | Zoning |
|---|---|
| Size: | 1/2" |
| Voltage: | 24 VAC |
| Connection Type: | Sweat |
| Hertz: | 60 |
| Amperage: | 0.48 |
| Flow Capacity (Cv): | 4.9 |
| Max Operating Pressure: | 300 psi |
| Body Pattern: | 3-Way |
| Fluid Temperature Range: | 20°F to 220°F |
| Position: | Normally Closed |
| End Switch: | Yes |
You would need to specify at the time of order. This particular zone valve is normally closed.
The 3/4" valve is equivalent to about 8.4" of pipe when calculating flow, while the 1" valve equals 47.4". Since the bore sizes on these valves are about the same, stepping up a size probably wouldn't be worth it.
This valve has one of the highest CV ratings in the market. CV= the amount of 60 degree water in gal/min. flowing through a fully open valve at 1 psi. It is the least resistant to flow than most other zone valves. The flow thru one part of a pipe is the same as the flow thru any other part of the pipe. What happens is the water speed up passing thru the valve. The 3/4" and 1" valve are the same except for the size of the copper pipe that can be soldered to it. You know, the max flow thru 3/4" pipe is about 4 gal/min. (about 3'/sec.). If you need that flow you can always use a bigger pump.
The basic valve on for every pipe size of Zone Sentry is 1/2 inch. You gain nothing by going to a larger pipe size hoping to get more flow. I have used many of these in all sizes. The small sized ball opening does not seem to have any negative affect on water flow or heat capacity. These are the only kind of zone valves I install now. The N.O. valves are also very effective in situations where you want to drain a system when there is a loss of power as in a solar draindown system.
This valve is only recommended for closed-loop systems. It will rust in an open system. You may want to take a look at Taco's geothermal zone valves, which are designed for use in open systems.
I have one of these setup in a open system, geothermal pump / dump. It has worked flawlessly, positive shut-off between the 60psi well system and 0psi dump.
The ESP valves are obsolete, having been replaced first by Taco's EBV valves and now by the Zone Sentry. The Zone Sentry head (part ZA024Q4A1) works with both the ESP and EBV valve bodies.
Please refer to the chart on the right side of the following document: http://s3.pexsupply.com/manuals/1296597322000/46579_PROD_FILE.pdf
Yes, they do.
Yes, it can be positioned vertically.
The life expectancy of these motors is about 7-12 years.
It can be sweated on either side. See page 1 of the manual below for more information. http://s3.pexsupply.com/manuals/1296597322000/46578_PROD_FILE.pdf
This valve is bi-direction so it does not matter which side you connect to the boiler.