| Type: | Combustion Tool |
|---|---|
| Application: | HVAC |
| Range: | 0 to 1000PPM (2000PPM with 5 minute max exposure time) |
| Initial accuracy at 73°F±9°F, <75%RH: | 0-15ppm ±5% reading ±1 ppm after zeroing, 16-35ppm ±5% reading ±2 ppm after zeroing, 36-1000ppm ±5% reading ±5ppm after zeroing |
| Display: | Updates real-time |
| CO Air Sample Temperature Range: | 32 to 105°F |
| Operating Environment: | 32 to 122ºF (0 to 50°C) |
| Sensor Type: | Electrochemical (specific to CO) |
| Sensor Calibration: | Factory calibrated on 205ppm |
| Long Term Drift: | <5% / year (depending on use) |
| Battery Type: | 9V |
| Battery Life: | 150 Hours |
| Auto-Off: | 15 minutes |
The sensors come factory calibrated, you would just have to replace it.
That type is a chemical sensor, when it's over exposed and won't clear to 0, you just replace it
The SCM4 does not come with a case SKU: ANC8 would be a suitable case for it.
This CO detector can be connectedwith the AOXP2 combustion kit hand pump for use in testing the carbon monoxide content in a flue. The AOXP2 Can be found here on our website: http://www.supplyhouse.com/Fieldpiece-SCM4-SCM4-Carbon-Monoxide-Detector