Zero Governors are gas pressure regulators that reduce incoming line pressure down to near-zero or atmospheric pressure at the outlet, used to feed burners, nozzle mixers, and proportional pre-mixers that require a balanced air-to-gas ratio. Maxitrol builds its zero governor line in sizes from half-inch through three-inch connections, with outlet pressure ratings around one psi on the smaller R400Z and R500Z models and up to five psi on the larger 210 series. Maxitrol's regulators work with natural gas, manufactured gas, mixed gases, liquefied petroleum gas, and LP gas-air mixtures, which covers most fuel types found on commercial and industrial combustion equipment. Installers working on gas-fired boilers, steam generators, industrial furnaces, and ovens rely on a properly sized zero governor to keep the air-fuel ratio steady as burner demand changes. Choosing the correct size and pressure rating for the connected burner keeps combustion efficient and prevents a governor from becoming the weak link in an otherwise well-tuned system.
Subcategories
Buying Guide
Start with the connection size already on the burner or mixing device. Maxitrol's zero governor lineup runs from half-inch connections up through three-inch, so matching the governor to the existing pipe size avoids adding a bushing that can throw off the pressure drop across the regulator. Next, check the outlet pressure rating the equipment calls for. Smaller R400Z and R500Z models are rated around one psi outlet, while the larger 210 series models reach up to five psi, so pulling the burner manufacturer's spec sheet before ordering prevents a mismatch that leaves the burner starved or overfed. Confirm the fuel type running through the system. Zero Governors are built for natural gas, manufactured gas, mixed gases, liquefied petroleum gas, and LP gas-air mixtures, which covers most combustion equipment found on commercial and industrial jobs, but confirming compatibility against the specific fuel blend on site avoids a regulator that isn't rated for it. Match the governor to the application. The 210 series is sized for gas-fired boilers, steam generators, industrial furnaces, and ovens with higher demand, while the R400Z and R500Z models suit smaller burners, nozzle mixers, and proportional pre-mixers. Have a technician verify the installed governor holds outlet pressure steady across the burner's full firing range, since a governor that drifts under load points to an incorrect size or a unit that needs servicing.
Frequently Asked Questions
What does a zero governor actually do?
A zero governor reduces incoming gas line pressure down to near-zero or atmospheric pressure at the outlet, rather than stepping it down to a fixed positive pressure like a standard appliance regulator. Near-zero outlet pressure lets a burner's own air-gas mixing system pull fuel in proportion to combustion air demand. Nozzle mixers, proportional pre-mixers, and ratio-controlled burners depend on this balanced pressure to keep the air-fuel ratio correct as firing rate changes. Sizing and installing the governor correctly keeps that ratio stable across the burner's full range.
What sizes do Maxitrol zero governors come in?
Maxitrol's zero governor lineup runs from half-inch connections on the R400Z and R500Z models up through three-inch connections on the larger 210 series. Matching the governor size to the existing burner or mixer connection avoids adding a bushing that changes the pressure drop through the regulator. Smaller sizes suit residential and light commercial burners, while the larger 210 series handles higher-demand equipment. Checking the connection size on the existing gas train before ordering prevents a mismatch.
What outlet pressure do zero governors provide?
Outlet pressure ratings vary by model, with the R400Z and R500Z rated around one psi and the larger 210 series models rated up to five psi. Matching this rating to what the connected burner or mixer requires is a key step before installation. A governor that doesn't match the required outlet pressure can starve or overfeed the burner, both of which throw off combustion efficiency. Pulling the burner manufacturer's spec sheet confirms the correct pressure rating before ordering.
What fuel types work with a zero governor?
Zero governors from Maxitrol are built for natural gas, manufactured gas, mixed gases, liquefied petroleum gas, and LP gas-air mixtures. Coverage across that range spans most fuel types found on commercial and industrial combustion equipment. Confirming the specific fuel blend running through a system against the governor's rating avoids a regulator that isn't suited to it. Checking compatibility before installation is a quick step that prevents a costly mismatch later.
What equipment typically uses a 210 series zero governor?
The 210 series, including the 210DZ, 210EZ, and 210GZ models, is built for gas-fired boilers, steam generators, industrial furnaces, and ovens. Larger connections in this series, from 1-1/2 inch through 3 inch, with outlet pressure up to five psi, suit high-demand combustion equipment rather than small residential appliances. Smaller R400Z and R500Z models cover lighter-duty burners and pre-mixers instead. Matching equipment demand to the correct series avoids undersizing the gas supply to the burner.