Apollo RVW60/61 Relief Valves are bronze safety relief valves built to protect hot water heating boilers and similar closed systems from dangerous overpressure and overtemperature conditions. The RVW61 line uses an oversized outlet relative to its inlet, such as a 3/4 inch inlet paired with a 1 inch outlet on the 1061436 model, which is rated for 3,879,000 BTU per hour at a 160 psi set pressure. Other set pressures are available on the same 3/4 inch by 1 inch connection, including a 150 psi option rated at 3,655,000 BTU per hour, along with larger 1-1/4 inch by 1-1/2 inch models rated up to 5,849,000 BTU per hour at 80 psi. Installers pick a specific model based on the BTU capacity and set pressure a given boiler or water heater setup requires, since undersizing a relief valve leaves a system without adequate overpressure protection. Getting the set pressure, connection size, and BTU rating right on the first order keeps a hot water heating installation compliant and safe to operate.
Subcategories
Buying Guide
Selecting the correct Apollo RVW60/61 Relief Valve starts with the system's actual BTU output, not just the boiler or water heater's nameplate horsepower. Pulling the BTU rating directly from the equipment's data plate and matching it against the valve's rated discharge capacity at the intended set pressure is the only reliable way to confirm adequate protection.
Set pressure comes next, and it needs to match the system's maximum allowable working pressure exactly. A valve set too high won't open before the system exceeds a safe limit, while one set too low trips more often than necessary and wastes water and energy on nuisance discharges.
Inlet size has to match the boiler or water heater's relief valve tapping, which is typically 3/4 inch on residential equipment and larger on commercial units. From there, deciding between the RVW60 and RVW61 comes down to outlet capacity: if the calculated BTU load exceeds what the standard same-size outlet can discharge, the RVW61's oversized outlet becomes necessary rather than optional.
Finally, confirming the connection type on an Apollo RVW60/61 Relief Valve, FNPT threading is standard across the line, and checking that the discharge piping downstream can handle the valve's full rated flow rounds out a proper installation. Skipping any one of these checks, BTU capacity, set pressure, inlet size, or outlet sizing, risks either an undersized safety device or a valve that doesn't fit the existing plumbing.
Frequently Asked Questions
What's the difference between the Apollo RVW60 and RVW61 relief valve?
The RVW60 uses a standard, same-size inlet and outlet connection, while the RVW61 steps the outlet up one size larger than the inlet, such as a 3/4 inch inlet paired with a 1 inch outlet. That oversized outlet gives the RVW61 more discharge capacity at the same inlet size. Choosing between them depends on whether the system's calculated BTU load exceeds what the standard outlet can safely discharge.
What set pressures are available for Apollo RVW60/61 relief valves?
Apollo RVW60/61 Relief Valves are available with set pressures ranging up to 160 psi, with specific models rated at pressures like 80 psi, 150 psi, and 160 psi depending on the part number. The set pressure needs to match the boiler or water heater's maximum allowable working pressure exactly. Checking the equipment's data plate before ordering confirms the correct set pressure.
What size relief valve does a residential water heater need?
Connection size needs to match the water heater's relief valve tapping, commonly 3/4 inch on models like the Apollo RVW61 1061436. Matching the BTU rating on the valve to the water heater's actual BTU input, not just the tank size, determines whether that connection size delivers enough discharge capacity. Checking the data plate on the water heater confirms both the required BTU rating and set pressure.
Are Apollo RVW60/61 relief valves rated for BTU capacity or just pressure?
Apollo RVW60/61 Relief Valves carry both a set pressure and a BTU per hour discharge rating, since a relief valve has to pass enough volume, not just open at the right pressure, to protect the system. The 1061436 model, for example, is rated for 3,879,000 BTU per hour at 160 psi. Matching both numbers to the system's actual load and pressure is necessary for adequate protection.
Can an RVW60 be replaced with an RVW61 on the same system?
Swapping in an RVW61 generally works as long as the inlet connection size matches the original tapping, since the RVW61's larger outlet doesn't change how it threads into the boiler or water heater. The main consideration is confirming the set pressure and BTU rating still match the system's requirements. Checking the outlet-side piping can accept the larger connection avoids a fitting mismatch during installation.