| Application: | Zoning |
|---|---|
| Voltage: | 24V |
| Operating Range: | 24V +/- 10% VAC |
| Max Close-Off PSI: | 17 psi/39.2 feet of head |
| Wiring: | Four-Wire |
| Type: | Motorized |
| Max Number of Actuators: | 6 MVAs (50VA transformer) 9 MVAs (75VA transformer) 12 MVAs (100VA transformer) |
| Used With: | TruFLOW Manifolds |
| Current Draw Range: | 0.29 Amps |
You can always check the actuator with a zone meter to see if the unit is opening and closing based on a call for heat.
Sure, just look at the front of the actuator. If the needle on the valve is in the open position all the time, just disconnect one set of the red and yellow wires from the thermostat connection. If the valve stays open replace it. If it closes, then reopens when you reconnect the themostat wires, your themostat may need replacing.
Please take a look at this document: http://s3.pexsupply.com/manuals/1291296857222/42040_PROD_FILE.pdf
The A3010522 is a thermal 4 wire unit and is slow opening (about 3-5 mins. to fully open), the A3020522 is a motorized 4 wire unit and is fast acting (opens in about 4 secs.), and the the A3020416 is a thermal 2 wire unit and is slow opening (about 3-5 mins. to fully open). All three are actuators and do the same thing as the end result, but each does it differently. So you can use any of them, it just depends on how you want it done.
The 10 loop manifold A2641000 is compatible with this actuator, A3020522. Two components you will definitely need are fitting assemblies (20) A4020625 to connect the PEX loops to the manifold and supply/return adapters. The other necessary components will depend on your system setup. Some common system components include pump, switching relay, transformer, and thermostats.