| Amperage: | 1 |
|---|---|
| Application: | Heat Pump Single-Stage (Heat/Cool) |
| Stages: | 1 Heat/1 Cool |
| Programmability: | Programmable 5-2 Day |
| User Interface: | Push Button |
| Mount: | Horizontal |
| Options: | Fan Control |
| Power Method: | Hardwired Battery |
| Changeover: | Manual |
| Temperature Range (F): | 40°F - 99°F |
| Max Temp Differential: | 1°F |
| Operating Humidity: | 5 to 90% RH, non-condensing |
| Voltage: | Low voltage 24V 750mV |
| Wattage: | 0.4 to 30 |
| Wiring: | C W Y G B O |
| Frequency: | 50 Hz 60 Hz |
| Color: | White Premier White |
| Height: | 3-13/16" |
| Width (Inches): | 5-3/8" |
| Depth (Inches): | 1-1/4" |
You can, but you would also need a control that is able to adapt to low-voltage thermostats and 4-wire actuators in order to link the thermostats to the actuators. We'd recommend a Taco zone valve control.
From what I can see, this thermostat does not have the capability to adjust the run time. It has a minimum off-time in order to protect the compressor, but even that is not adjustable.
I'm no expert , but if You place the fan switch in the on position instead of auto its not so noticeable. Or maybe your thermostat is not placed in an appropriate spot. Hope this helps. Good luck.
There would be no issue using this thermostat for cooling only. Wiring should not be a major issue, but you might want to look at the wiring diagram (see link below) prior to making a final decision. http://s3.pexsupply.com/manuals/1277918330238/33866_PROD_FILE.pdf
Please refer to the following link for the manufacturer's Installation Guide for this thermostat: http://s3.pexsupply.com/manuals/1277918330238/33866_PROD_FILE.pdf
You need to change Installer Setup Function 13 from setting 1 (the default) to 0. To enter the installer setup menu, hold down the two arrow buttons until the display changes. The function number will be on the left, with the setting number to its right. Use the down arrow to change settings, the up arrow to advance to the next function, and hold both arrows to exit the menu and save your settings.
No, only Honeywell's VisionPRO and Prestige thermostats are compatible with outdoor sensors.
According to the manufacturer, the TH4110D thermostat will operate a 24-volt gas control system that was using a T8085 thermostat.
No problem with that-you can't go wrong with this choice.
No problem. You made a great choice with the th4110d.
Yes, this thermostat is appropriate to use with a propane stove.
Here is a link to the installation manual: http://s3.pexsupply.com/manuals/1277918330238/33866_PROD_FILE.pdf .
The wiring will have to be confirmed by an installer to be compatible with the thermostat you would like to switch out to. Please confirm with a technician when it comes to the wires.