Powermite MT Series Globe Valves are HVAC terminal unit control valves used to modulate hot or chilled water flow to fan coils, reheat coils, and other zone terminal equipment. Siemens builds the line in valve sizes from 1/2 inch to 1 inch, rated to ANSI Class 250, with Cv ratings that run from 0.4 on the smallest 1/2-inch body to higher flow capacities on the 3/4-inch and 1-inch bodies. The 1/2-inch and 3/4-inch bodies are forged brass, while the 1-inch body switches to bronze for the larger flow path. A stainless steel stem and metal-to-metal seat design pair with a 7/32-inch actuator stroke, and the valve accepts either a pneumatic or electronic actuator depending on the control system already installed. Because the same stroke and mounting pattern carries across sizes, controls contractors can standardize actuator stock across a job while still matching valve body and Cv to each terminal unit's flow requirement.
Subcategories
Buying Guide
Cv rating is the starting point for specifying a globe valve, not valve size alone. Calculate the required Cv from the terminal unit's design flow and the pressure drop the coil can tolerate, then choose a Powermite MT Series Globe Valve sized to deliver that Cv without oversizing the valve and losing control resolution. Body material follows valve size on this line: 1/2-inch and 3/4-inch bodies are forged brass, while the 1-inch body is bronze to handle the larger flow path, so confirm the medium is compatible with both materials before specifying, particularly on systems running water-glycol mixes. Two-way valves work for simple on/off or modulating control to a single coil, while three-way valves handle mixing or diverting duties on systems that need constant flow through a coil independent of the control signal; choosing the wrong configuration for the application usually means a callback to swap the valve body. Actuator compatibility matters just as much as the valve body itself. Every MT Series valve uses the same 7/32-inch stroke, so pneumatic and electronic actuators from the same family can be standardized across a job even when valve sizes and Cv ratings differ from one terminal unit to the next. Confirm the medium temperature and pressure class match the application, since these valves are built for water, water-glycol, and low-pressure steam service within their ANSI Class 250 rating rather than higher-pressure steam systems.
Frequently Asked Questions
How is Cv used to size a globe valve?
Cv describes how much water flows through the valve at a given pressure drop, and it's calculated from the terminal unit's design flow and allowable pressure drop across the coil. Powermite MT Series valves range from 0.4 Cv on the smallest 1/2-inch body to higher ratings on the 3/4-inch and 1-inch bodies. Oversizing the Cv for the application reduces control resolution, so matching Cv to actual design flow matters more than matching valve size to pipe size alone.
What's the difference between the brass and bronze valve bodies?
1/2-inch and 3/4-inch MT Series valves use forged brass bodies, while the 1-inch valve uses a bronze body to handle its larger flow path. All sizes pair the body with a stainless steel stem and metal-to-metal seat. Confirming the medium, including any water-glycol content, against the body material is worth checking before specifying a valve for a given system.
Can the same actuator work across different valve sizes?
Every MT Series globe valve uses the same 7/32-inch actuator stroke, whether it's a 1/2-inch or 1-inch body. That consistency lets controls contractors standardize on one actuator family across a job even when Cv and valve size vary by terminal unit. Both pneumatic and electronic actuators are compatible with the stroke across the line.
When does a project need a three-way valve instead of a two-way valve?
Three-way valves are used when a system needs constant flow through a coil regardless of the control signal, mixing or diverting flow between two paths instead of shutting flow off entirely. Two-way valves work for straightforward on/off or modulating control where variable flow through the coil is acceptable. Choosing the wrong configuration for a given terminal unit typically means a service call to swap the valve body later.
What medium and temperature range are these valves rated for?
Powermite MT Series valves are rated for water, water-glycol mixtures, and low-pressure steam service within their ANSI Class 250 rating. Medium temperature range runs from 35 to 250 degrees Fahrenheit. Confirming the system's actual operating medium and temperature against those limits avoids specifying a valve outside its intended service.