| Width (Inches): | 3-1/2" |
|---|---|
| Material: | Aluminum |
| Tubing Compatibility: | PEX-a PEX-b |
| Application: | 1/2" PEX |
| Length (Inches): | 48" |
| Height: | .675" |
| Diameter: | 0.640" (Internal Channel) |
| Wall Thickness: | .050" |
The water heater you need will be based on BTU load and your fuel source. Tankless water heaters do not come with pumps.
A pump is highly recommended since just the convection alone will not move the water fast enough to thoroughly heat all of the zone.
These plates are only designed for use with PEX tubing.
The maximum water temperature for suspended/joist trak is 170°F. The maximum surface temperature of the wood floor you would want is 82°F. As long as your system can run meeting those limits you are fine to install the radiant system.
You should insulate the joist bay. You can use batting or spray foam.
Yes, they can. Joist Trak panels are compatible with any standard PEX.
You can use silicone. We do not recommend it, however, because it will not actually cut down on noise. The expansion of the metal when it gets hot produces sound, not the tubing itself.
You can remove the baseboards completely, as long as your new system will be capable of meeting your demand for heat. Some people choose to leave baseboards in place to serve as a backup heating source on days of extreme temperatures. When using Joist Trak panels, we recommend that you insulate the entire joist bay.
Joist Trak panels will not make the wood buckle if the system is installed properly. Make sure you lay a subfloor thick enough to prevent the wood from reaching 82 °F (the temperature at which wood may start to dry out).
Make sure that no panels are touching or overlapping, ensure that all the screw holes in the panels are in use, and insulate the bays with at least R-19.
Yes, you can use this system with that heater as long as the heater has enough BTUs to heat the space.